Product Placeholder

Altivar 61

Repair Options

  Standard:  2-3 days

  Urgent:  24-48 hours*

✓  Service Exchange:  48-hour replacement*

✓  Spare Unit:  Same unit as the original*

* Services subject to availability

About

The Altivar 61 is the fan and pump member of Schneider Electric’s Altivar 61 and Altivar 71 pair, catalogued for variable torque duty and also usable on constant torque loads that do not require high starting current.

The range covers 0.37 to 800 kW across 89 catalogue numbers, on supply classes from 200-240 V to 500-690 V. H is the standard drive on a heatsink and W the IP54 or UL Type 12 build, and the rating block is a kW multiplier, so 075 is 0.75 kW and C75 is 750 kW. X means no class A EMC filter, Z means no graphic display terminal, and D no DC choke, expecting an external reactor.

Schneider has phased the range out and maps the ATV630 onto the ATV61H and the ATV650 onto the ATV61W. It warns that the ATV600 has no provision for a dynamic braking resistor or a DC bus connection, so an ATV61 wired to either has no like for like successor.

Key Features

  • Power Removal (PWR) safe torque off input to EN 954-1 category 1 or category 3

  • 120% overload for 60 seconds on the smaller ratings, 110% on the largest

  • Speed range 1:100 in open loop, 1:1000 in closed loop with encoder feedback

  • Modbus and CANopen built in on the RJ45 port

  • Integrated class A EMC filter on most references; the ATV61HpppM3X ships without one

  • Motor thermal protection by speed-compensated I2t with the thermal state saved at power down

Range Specifications

ManufacturerSchneider Electric
SeriesAltivar 61
Motor TypesThree-phase synchronous and asynchronous motors
Voltage Groups200-240 V (1 phase); 200-240 V (3 phase); 380-480 V (3 phase), IP20 protection; 380-480 V (3 phase), IP54 ATV61W with an integrated category C2 EMC filter; 500-600 V (3 phase); 500-690 V (3 phase)
Protection ClassATV61H smaller frames: IP20, IP41 on the upper part, IP54 on the isolated power component and heatsink section. ATV61HD55M3X, HD75M3X, HD90N4 to HC63N4 and HC11Y to HC80Y: IP00, IP41 upper part, IP30 front panel and sides. UL Type 1 with accessory VW3A92pp. ATV61W: IP54 / UL Type 12, 0.75 to 90 kW
Speed Range1:100 in open loop mode
Overload110% to 120% for 60 s
Acceleration / Deceleration RampsLinear, adjustable separately from 0.01 to 9999 s (parameter setting range); S, U or customised profiles; automatic adaptation of the deceleration ramp, which can be inhibited
Motor Power Range0.37 to 800 kW
Nominal Current Range2.3 A (ATV61H075N4) to 1,188 A (ATV61HC63N4)
Integrated CommunicationModbus and CANopen
Standards And CertificationsUL 508C, CSA, C-Tick, NOM 117, GOST; ABS and DNV marine; CE marked to the low voltage (2006/95/EC) and EMC (89/336/EEC) directives
Product StatusObsolete. Schneider states that Altivar 61 drives are no longer available and that the ATV61 was phased out of production in the US in 2016. The ATV630 replaces the ATV61H and the ATV650 replaces the ATV61W; no end of service date is published

Altivar 61 Models

Series/voltage groupModelCapacity, kWCurrent, ADimensions (W x H x D), mm
Altivar 61 series, voltage 200-240 V (1 phase)ATV 61H075M30.373130x230x175
Altivar 61 series, voltage 200-240 V (1 phase)ATV 61HU15M30.754.8130x230x175
Altivar 61 series, voltage 200-240 V (1 phase)ATV 61HU22M31.58155x260x187
Altivar 61 series, voltage 200-240 V (1 phase)ATV 61HU30M32.211155x260x187
Altivar 61 series, voltage 200-240 V (1 phase)ATV 61HU40M3313.7155x260x187
Altivar 61 series, voltage 200-240 V (1 phase)ATV 61HU55M3417.5175x295x187
Altivar 61 series, voltage 200-240 V (1 phase)ATV 61HU75M35.527.5210x295x213
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61H075M30.754.8130x230x175
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HU15M31.58130x230x175
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HU22M32.211155x260x187
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HU30M3313.7155x260x187
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HU40M3417.5155x260x187
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HU55M35.527.5175x295x187
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HU75M37.533210x295x213
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD11M3X1154230x400x213
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD15M3X1566230x400x213
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD18M3X18.575240x420x236
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD22M3X2288240x420x236
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD30M3X30120320x550x266
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD37M3X37144320x550x266
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD45M3X45176320x550x266
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD55M3X55221320x920x377
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD75M3X75285320x920x377
Altivar 61 series, voltage 200-240 V (3 phase)ATV 61HD90M3X90359360x1022x377
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61H075N40.752.3130x230x175
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HU15N41.54.1130x230x175
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HU22N42.25.8130x230x175
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HU30N437.8155x260x187
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HU40N4410.5155x260x187
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HU55N45.514.3175x295x187
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HU75N47.517.6175x295x187
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD11N41127.7210x295x213
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD15N41533230x400x213
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD18N418.541230x400x213
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD22N42248240x420x236
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD30N43066240x550x266
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD37N43779240x550x266
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD45N44594320x630x290
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD55N455116320x630x290
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD75N475160320x630x290
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HD90N490179320x920x377
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HC11N4110215320x920x377
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HC13N4132259360x1022x377
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HC16N4160314340x1190x377
Altivar 61 series, voltage 380-480 V (3 phase), IP20 protectionATV 61HC22N4200427440x1190x377

These 45 rows cover 38 of the 89 distinct Altivar 61 catalogue numbers; the seven 200-240 V single-phase rows reuse the same catalogue numbers as the three-phase rows at a one-rating derate. Not shown: the tail of the 380-480 V IP20 group (ATV 61HC25N4, HC31N4, HC40N4, HC50N4 and HC63N4), the whole 380-480 V IP54 ATV61W group, the 500-600 V group (ATV 61HU22S6X to HU75S6X) and the whole 500-690 V group (ATV 61HU30Y to ATV 61HC80Y), so please contact Inverter Drive Repair if your drive is one of these.